Skip to main content

13. DIR Error Codes

D
Written by Dheeraj Nagar

This table describes the error codes with all other required information:

Error Code

Error Message

DIR is Generated

Send to customer (North America region only)

Description

Action requires

200

Health Score is Generated Successfully

Yes

The DIR has been generated successfully with all sections and accurate data.

201

Chiller failed to meet peak load.

Yes (Only Alarms, Chiller Logs, and Trend Charts sections)

It indicates the chiller failed to meet the peak load threshold during the reporting period.

202

Chiller average load below 20%

Yes (Only Alarms, Chiller Logs, and Trend Charts sections)

It indicates the average load of the chiller during the reporting period was less than 20%.

203

No more than 30 minutes continuous operation

Yes (Only Alarms, Chiller Logs, and Trend Charts sections)

It indicates the chiller did not run consistently higher hours during the reporting period.

204

Offline/Pending in AHP

No

Yes (It contain the reason)

It indicates the chiller onboarding is incomplete and needs to be addressed by the field.

Field action is required to take the chiller back online.

205

Chiller Migration Issue or Backend Onboarding Issue

No

No

It indicates that the chiller is not fully onboarded, and data was never sent to AHP but is online in the SMART platform.

AHP support team help is required to resolve the C2C (cloud to cloud) migration issues.

206

Missing Design Data

Yes (Inaccurate data for some sections)

It indicates the necessary design data for the chiller is not available.

207

Pack Load Bricks class Not Found

No

No

It indicates that the chiller load was not ascertained during the report period.

AHP Tiger team helps to resolve this issue.

208

Circuit Load Not Meet

Yes

It indicates the circuit was not loaded sufficiently during the reporting period.

400

Report Generation Failed

No

It indicates the DIR for the specific work order has not been generated successfully.

You can retry again after 30 minutes.

500

Report Generation Failed

No

It indicates the DIR for the specific work order has not been generated successfully.

You can retry again after 30 minutes.

Customer DIR is currently available in North America and will be launched in other regions soon.

Did this answer your question?